318-B H05Z1Z1-F EN 50525-3-11 Flexible Multicore LSZH Insulation and Sheath Harmonised Cable Copper Wire Used As Indoor General Wiring
Application
Used as an indoor general wiring cable primarily for installations in public areas. Examples include use on pendant
lighting drops or as a general supply lead within hospital or airport projects. For installation where fire, smoke emission
and toxic fumes create a potential risk to life and equipment.
Construction
Conductor Class 5 flexible copper conductor
Insulation LSZH (Low Smoke Zero Halogen) Type TI6
Core Identification 2 core: Blue, Brown
3 core: Green/Yellow, Blue, Brown
4 core: Green/Yellow, Brown, Black, Grey
5 core: Green/Yellow, Brown, Black, Grey, Blue
Sheath LSZH (Low Smoke Zero Halogen) Type TM7
Sheath Colour White, Black
Characteristic
Voltage Rating (Uo/U) 300/500V
Temperature Rating +5°C to +70°C
Minimum Bending Radius 5 x overall
Temperature Rating +5°C to +70°C
Minimum Bending Radius 5 x overall
Standards
EN 50525-3-11 (HD21.14), EN 60228
Flame Retardant according to IEC/EN 60332-1-2
Flame Retardant according to IEC/EN 60332-1-2
Dimensions
NO. OF CORES | NOMINAL CROSS SECTIONAL AREA |
NOMINAL THICKNESS OF INSULATION |
NOMINAL OVERALL DIAMETER |
NOMINAL WEIGHT |
mm2 | mm | mm | kg/km | |
2 | 0.75 | 0.6 | 6.3 | 57 |
2 | 1 | 0.6 | 6.6 | 65 |
2 | 1.5 | 0.7 | 7.4 | 84 |
2 | 2.5 | 0.8 | 9 | 130 |
2 | 4 | 0.8 | 10.4 | 180 |
3 | 0.75 | 0.6 | 6.7 | 68 |
3 | 1 | 0.6 | 7 | 78 |
3 | 1.5 | 0.7 | 8 | 107 |
3 | 2.5 | 0.8 | 9.9 | 163 |
3 | 4 | 0.8 | 11.1 | 212 |
4 | 0.75 | 0.6 | 7.3 | 83 |
4 | 1 | 0.6 | 7.9 | 100 |
4 | 1.5 | 0.7 | 9 | 134 |
4 | 2.5 | 0.8 | 10.8 | 201 |
4 | 4 | 0.8 | 12.2 | 290 |
5 | 0.75 | 0.6 | 8.1 | 103 |
5 | 1 | 0.6 | 8.3 | 130 |
5 | 1.5 | 0.7 | 10.4 | 170 |
5 | 2.5 | 0.8 | 12.1 | 255 |
5 | 4 | 0.8 | 15 | 360 |