H05Z-K / H07Z-K Single Core Bare Copper Wire LSZH Wire Cable PVC Insulation Flexible Copper Conductor Cable
H05Z-K / H07Z-K
CONSTRUCTION
Conductor:Class 5 flexible copper conductor according to BS EN 60228
Insulation:LSZH (Low Smoke Zero Halogen) Type EI5 thermo setting insulation according to BS EN 50363-5
CHARACTERISTICS
Voltage Rating (Uo/U)
H05Z-K – 0.5mm2 to 1mm2 : 300/500V
H07Z-K – 1.5mm2 to 6mm2 : 450/750V
Temperature Rating:-25°C to +90°C
Minimum Bending Radius:4 × overall diameter
TYPE |
Nominal CrossSectional Area
mm² |
Thickness of
Insulation mm |
Nominal Overall Diameter | Min. Resistance ofInsulation at 90°C MΩ/km | |
Lower Limitmm | Upper Limit mm | ||||
H05Z-K | 0.5 | 0.6 | 1.9 | 2.4 | 0.015 |
0.75 | 0.6 | 2.2 | 2.8 | 0.011 | |
1 | 0.6 | 2.4 | 2.9 | 0.01 | |
H07Z-K |
1.5 | 0.7 | 2.8 | 3.5 | 0.01 |
2.5 | 0.8 | 3.4 | 4.3 | 0.009 | |
6 | 0.8 | 4.4 | 5.5 | 0.006 |
APPLICATION
In pipes or ducts and internal wiring of appliances with maximum operating temperatures of 90°C, and generally in areas (such as public and government buildings) where smoke and toxic fumes may cause a threat to life and equipment. The cables produce no corrosive gases when burnt which is particularly important where electronic equipment is installed.