H07V-K/ (H)07V-K PVC-Single Cores Fine Wire Stranded Fine Copper Wire Cable
H07V-K/ (H)07V-K
CABLE CONSTRUCTION
Conductor
Bare Cu-conductor, to DIN VDE 0295 cl.5, fine-wire, BS 6360 cl.5, IEC 60228 cl.5
Core insulation of PVC compound type TI1 to DIN VDE 0207-363-3 / DIN EN 50363-3 and IEC60227-3s
TECHNICAL DATA
PVC single cores to DIN VDE 0285 – 525 – 2 – 31 /DIN EN 50525 – 2 – 31 and IEC 60227 – 3
Temperature range flexing - 5°C to +70°C fixed installation - 30°C to + 80°C
Nominal voltage 450/750 V
Test voltage 2500 V
Insulation resistance min . 10 MΩ x km
Minimum bending radius fixed installation core Ø≤ 8 mm: 4x core Ø
core Ø > 8-12 mm: 5x core Ø
core Ø > 12 mm: 6x core Ø
APPLICATION
These single cores are suitable for laying in tubes, under and surface mounting of plasters and also in closed installation conduits. These are not allowed to install for direct laying on cable trays, channels or tanks. These types are permitted for the inner wiring of equipment, distributor and switchboards and also for protective laying to the lighting with a nominal voltage up to 1000 V alternating current or up to 750 V direct current against earth.
H07V-K/ (H)07V-K DIMENSION
Cross section area | Outer diameter approx. | Copper weight |
mm² | mm | kg / km |
1.5 | 2.8 - 3.4 | 14.4 |
2.5 | 3.4 – 4. 1 | 24.0 |
4 | 3.9 – 4.8 | 38.0 |
6 | 4.4 - 5.3 | 58.0 |