Li2ycy (TP) Class 5 Oxygen Free Copper Stranded Conductor Braiding Screened Data Transmission Cable Electric Wire
Construction
Conductor | Class 5 oxygen free copper stranded conductor, based on VDE 0881, 7-wire |
Insulation | PE |
Core Identification | DIN 47100, refer to Appendix T9 |
Screen | Tinned-copper braiding |
Sheath | PVC (Polyvinyl Chloride) Colour: grey |
Characteristics
Test Voltage: Core/Core 2000V
Core/Screen 1000V
Temperature Rating:Fixed: – 5°C to +70°C
Fixed installation: -40°C to +80°C
Minimum Bending Radius:Fixed: 6 x overall diameter
Occasional flexing: 15 x overall diameter
Application
Particularly suitable for wiring data systems with transmission rates up to 10 Megabits per second, and is qualified for the RS422 and RS485 interfaces. For fixed and limited flexible installation, Can be used in dry or damp rooms. Signal-, control- and measuring cable, for transmission of low, sensitive signals and high bit rates.
Dimensions
No of pairs x CON. mm² | Outer diameter | Copper index | Weight |
mm2 | mm | kg/km | kg/km |
2 x 2 x 0.22 | 6.5 | 24.2 | 59 |
3 x 2 x 0.22 | 7.1 | 28.6 | 66 |
4 x 2 x 0.22 | 7.3 | 34.2 | 78 |
8 x 2 x 0.22 | 9.1 | 70 | 125 |
10 x 2 x 0.22 | 10.4 | 76 | 143 |
1 x 2 x 0.34 | 5.8 | 20 | 44 |
2 x 2 x 0.34 | 7.7 | 34.1 | 79 |
3 x 2 x 0.34 | 8.4 | 43 | 89 |
4 x 2 x 0.34 | 8.7 | 47 | 101 |
8 x 2 x 0.34 | 11 | 85.8 | 176 |
1 x 2 x 0.5 | 6.3 | 29 | 53 |
2 x 2 x 0.5 | 8.5 | 37 | 85 |
3 x 2 x 0.5 | 9.3 | 55 | 105 |
4 x 2 x 0.5 | 9.6 | 60 | 122 |
8 x 2 x 0.5 | 12.7 | 113.3 | 213 |
10 x 2 x 0.5 | 14.8 | 154 | 261 |
Write your message here and send it to us