steel wire armoured shielded pvc instrument cable multi pair overall screened armor instrumenttation cable

 multi pair overall screened armor instrumenttation cable  steel wire armoured shielded pvc instrument cable


Product Detail

Product Tags

PAS5308 PART2/TYPE1 INSTRUMENTATION CABLE, OVERALL SCREENED

Application

Manufactured to PAS5308, Instrumentation cables are intrinsically safe and designed for use in communication and instrumentation applications in and around process industries for transmission of signals in control systems. The signals can be analogue or digital from a variety of sensors and transducers.

 

Constructions

Conductor: Plain Annealed Copper Conductors

Insulation: Polyvinyl Chloride (PVC)

Arranged: Laid up to form pairs Bedding: Polyvinyl Chloride (PVC)

Screen: Collective aluminium / mylar tape screen complete with 0.5mm drain wire Sheath: Polyvinyl Chloride (PVC)

Sheath Colour: Blue or Black

The maximum period of operation is 15years

 

 

Installation Temperature: Above 0℃

Operating Temperature: -15℃ ~ 65℃

Rated Voltage: 300/500V

Test Voltage (DC): 2000V Between Conductors

2000V Between Each Conductor and Armour

 

Reference Standards

BS 5308 PAS5308

BS EN 50265

BS EN/IEC 60332-3-24

Flame propagation to BS4066 Pt1

 

General Characteristics

Conductor Size (mm2)

Conductor Class

Max. DCR (Ω/km)

Capacitance

Max.L/R Ratio (μH/Ω)

Max. Mutual Capacitance pF/m

Core to Screen

0.5

5

39.7

250

450

25

0.75

5

26.5

250

450

25

1.5

2

12.3

250

450

40

 

 

Identification of Cable Pairs

Pair No.

Colour

Pair No.

Colour

1

White

Blue

11

Black

Blue

2

White

Orange

12

Black

Orange

3

White

Green

13

Black

Green

4

White

Brown

14

Black

Brown

5

White

Grey

15

Black

Grey

6

Red

Blue

16

Yellow

Blue

7

Red

Orange

17

Yellow

Orange

8

Red

Green

18

Yellow

Green

9

Red

Brown

19

Yellow

Brown

10

Red

Grey

20

Yellow

Grey

 

PAS/BS5308 Part 2 Type 1: Collectively Screened Unarmoured

No. of Pairs

Conductor

Insulation Thickness (mm)

Sheath Thickness (mm)

Overall Diameter (mm)

Size (mm2)

Class

1

0.5

5

0.6

0.8

6.0

2

0.5

5

0.6

0.8

6.9

5

0.5

5

0.6

1.0

11.9

10

0.5

5

0.6

1.1

16.4

15

0.5

5

0.6

1.2

19.0

20

0.5

5

0.6

1.3

21.5

1

0.75

5

0.6

0.8

6.4

2

0.75

5

0.6

0.8

7.4

5

0.75

5

0.6

1.0

12.8

10

0.75

5

0.6

1.2

17.9

15

0.75

5

0.6

1.3

20.9

20

0.75

5

0.6

1.4

23.6

1

1.5

2

0.6

0.8

7.3

2

1.5

2

0.6

0.9

8.7

5

1.5

2

0.6

1.1

15.1

10

1.5

2

0.6

1.3

21.1

15

1.5

2

0.6

1.4

24.6

20

1.5

2

0.6

1.5

27.7

 

PAS/BS5308 Part 2 Type 1: Individually & Collectively Screened Unarmoured

No. of Pairs

Conductor

Insulation Thickness (mm)

Sheath Thickness (mm)

Overall Diameter (mm)

Size (mm2)

Class

2

0.5

5

0.6

0.9

9.7

5

0.5

5

0.6

1

12.6

10

0.5

5

0.6

1.2

18.0

15

0.5

5

0.6

1.3

20.9

20

0.5

5

0.6

1.4

23.6

2

0.75

5

0.6

0.9

10.4

5

0.75

5

0.6

1

13.5

10

0.75

5

0.6

1.2

19.4

15

0.75

5

0.6

1.4

22.8

20

0.75

5

0.6

1.5

25.8

2

1.5

2

0.6

1

12.1

5

1.5

2

0.6

1.1

15.8

10

1.5

2

0.6

1.4

22.9

15

1.5

2

0.6

1.5

26.6

20

1.5

2

0.6

1.6

30.1

 

 

PAS/BS5308 Part 2 Type 1: Multicore Collectively Screened Unarmoured

No. of Cores

Conductor

Insulation Thickness (mm)

Sheath Thickness (mm)

Overall Diameter (mm)

Size (mm2)

Class

2

0.5

5

0.6

0.8

6.0

3

0.5

5

0.6

0.8

6.3

4

0.5

5

0.6

0.8

6.9

6

0.5

5

0.6

0.8

8.1

10

0.5

5

0.6

0.9

10.4

20

0.5

5

0.6

1.0

13.5

2

0.75

5

0.6

0.8

6.4

3

0.75

5

0.6

0.8

6.8

4

0.75

5

0.6

0.8

7.4

6

0.75

5

0.6

0.9

8.9

10

0.75

5

0.6

1.0

11.5

20

0.75

5

0.6

1.1

14.8

2

1.5

2

0.6

0.8

7.3

3

1.5

2

0.6

0.8

7.7

4

1.5

2

0.6

0.9

8.7

6

1.5

2

0.6

0.9

10.3

10

1.5

2

0.6

1.0

13.3

20

1.5

2

0.6

1.2

17.4

 

 